The Gemini® 38AU series outdoor units and matched with the 40RU series indoor air handlers offer a wide variety of options for your HVAC application needs. This series is designed for long dependable operation whether it's a rooftop or on-the-ground installation. All GEMINI 38AU Condensing Units and 40RU Fan Coils use environmentally sound Puron® refrigerant. Together, they create a reliable split system that provides easy solutions to a wide range of commercial HVAC needs.
| Unit | Cooling Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | EER | IEER |
|---|---|---|---|---|---|---|
| 38AUQ07 / 40RUQ07 | 1 | 6 | 70.0 | 6.4 | 11.0 | 12.6 |
| 38AUQ08 / 40RUQ08 | 1 | 7.5 | 89.0 | 8.1 | 11.0 | 12.0 |
| 38AUQ12 / 40RUQ12 | 1 | 10 | 112.0 | 10.2 | 11.0 | 12.0 |
| 38AUQ16 / 40RUQ16 | 2 | 15 | 178.0 | 16.8 | 10.6 | 11.0 |
| 38AUQ25 / 40RUQ25 | 2 | 20 | 220.0 | 20.8 | 10.7 | 11.0 |
| Unit | Heating Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | COP |
|---|---|---|---|---|---|
| 38AUQ07 / 40RUQ07 | 1 | 6 | 66.0 | 5.9 | 3.30 |
| 38AUQ08 / 40RUQ08 | 1 | 7.5 | 87.0 | 7.7 | 3.30 |
| 38AUQ12 / 40RUQ12 | 1 | 10 | 106.0 | 9.4 | 3.30 |
| 38AUQ16 / 40RUQ16 | 2 | 15 | 178.0 | 15.3 | 3.40 |
| 38AUQ25 / 40RUQ25 | 2 | 20 | 214.0 | 17.9 | 3.50 |
| Unit | Heating Stages | Nominal Capacity (Tons) | Net Cooling Capacity (MBH) | Total Power (kW) | COP |
|---|---|---|---|---|---|
| 38AUQ07 / 40RUQ07 | 1 | 6 | 39.0 | 5.2 | 2.20 |
| 38AUQ08 / 40RUQ08 | 1 | 7.5 | 52.0 | 6.9 | 2.20 |
| 38AUQ12 / 40RUQ12 | 1 | 10 | 70.0 | 9.3 | 2.20 |
| 38AUQ16 / 40RUQ16 | 2 | 15 | 108.0 | 13.2 | 2.40 |
| 38AUQ25 / 40RUQ25 | 2 | 20 | 130.0 | 15.9 | 2.40 |
LEGEND
AHRI = Air-Conditioning, Heating and Refrigeration Institute
ASHRAE = American Society of Heating, Refrigerating and Air Conditioning, Inc.
EER = Energy Efficiency Ratio
IEER = Integrated Energy Efficiency Ratio
COP = Coefficient of Performance
NOTES
1. Rated in accordance with ARI Standard 340/360---07, as appropriate.
2. Ratings are based on:
- Cooling Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 35°C (95°F) db outdoor air temp.
- IEER Standard: 27°C (80°F) db, 19°C (67°F) wb indoor air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for minimum EER and IEER requirements.
Technical information
Estimates reflect the selected item and order timing. Dispatch is when your order leaves the supplier; arrival also depends on carrier transit and your destination.
Read shipping policy →Availability depends on the product, location and order requirements. Check the options above or contact our team with your SKU and delivery address.
Call (915) 598-8598 →